| KNX bus | 21–30 V DC via the KNX bus, <12 mA, <360 mW |
| Inputs | 4 floating (dry) contacts, each individually configurable |
| Input scanning | >12 V DC, input current 0.7 mA |
| Max. cable length | 100 m (1.5 mm² cross section) |
| Input functions | Switching, dimming, shutter control, scene, value sending, RGB and RGBW dimming, shift register, multiple operation, delay mode |
| Logic | 8 logic functions, 8 event groups |
| Terminals | KNX bus terminal; screw terminals 0.5–2.5 mm², max. 0.4 N·m |
| Ambient temperature | −5 °C to +45 °C (operation), −25 °C to +55 °C (storage), −25 °C to +70 °C (transport) |
| Humidity | < 93 %, non-condensing |
| Mechanical data | MDRC, 35 mm DIN rail, 36 × 90 × 64 mm, 0.1 kg |
| KNX Secure | Supported |