| KNX bus | 21–30 V DC via the KNX bus, <13.5 mA at 24 V, <11.5 mA at 30 V, <345 mW |
| Valve outputs | 6 channels, ≤300 mA per channel at 35 °C ambient |
| Drive voltage | 24 V AC or 230 V AC |
| Room temperature controllers | 6, heating and cooling mode, 2-point and PI control |
| Protection | Short-circuit and overload protection |
| Manual operation | One button per channel plus Man./Auto. button, with status LEDs |
| Terminals | KNX bus terminals; screw terminals 0.2–2.5 mm², 0.4 N·m |
| Ambient temperature | −5 °C to +45 °C (operation), −25 °C to +55 °C (storage), −25 °C to +70 °C (transport) |
| Humidity | < 93 %, non-condensing |
| Mechanical data | MDRC, 35 mm DIN rail (EN 60 715), 72 × 90 × 64 mm, 0.30 kg |
| KNX Secure | Supported |