Skip to content

Commissioning

The Universal8 is configured in ETS (version 5 or higher) using the Atios product database. There is no web interface.

  1. Add the Multifunctional Actuator with Secure, 8-Fold product database (.knxprod) to your ETS catalogue and drag the device into your topology.
  2. Assign the physical address: press the Prog button on the device (the red LED lights) and download the address.
  3. Open the Channel function window and set Product to 8-Fold.
  4. Assign each block of outputs (1–4 and 5–8) a function: Switch, Curtain AC, Curtain DC, Fan control, or Valve control. See Channel Functions for what each one does.
  5. Set the parameters for each channel, then download the application.

For secure commissioning, see KNX Secure.