Skip to content

Application Controller

If the DALI line has no central controller, or the one it has does not support IEC 62386-103, the coupler can drive the lights itself. In application controller mode it stops sending event notifications and sends DALI commands instead.

Enable it with a DALI configuration tool: address the device first, then switch on the application controller setting. Turning it off returns the coupler to input device mode.

Assigning commands

Each button is given a command for short press and a command for long press. The available commands are:

CommandWhat it does
OFFSwitches off
UP / DOWNDims up or down at the fade rate
STEP UP / STEP DOWNChanges the level by one increment
ON AND STEP UPSteps up, and switches on first if the light was off
STEP DOWN AND OFFSteps down, and switches off at the minimum level
RECALL MAX LEVEL / RECALL MIN LEVELGoes to the configured maximum or minimum
GO TO LAST ACTIVE LEVELSwitches on to the level the light had before
GO TO SCENERecalls one of scenes 0 to 15
DAPCGoes to a brightness you enter as a percentage
TCSets a colour temperature, for DT8 tunable white fixtures
NoneNo action

Targets

Each button addresses up to four targets. A target is a broadcast, one of groups G00 to G15, or a single address A00 to A63. When the button is operated, the targets are processed one after the other.

That is what lets a single button switch a group of ceiling lights and set the colour temperature of a second group in one press.

Device groups

The coupler can be assigned to up to 32 control device groups. These are groups of control devices such as couplers and sensors. They are not the luminaire groups that the commands above address, and the two numbering schemes are unrelated.