Installation

The Binary4 is a DIN-rail device (MDRC) for the electrical cabinet. It mounts on a 35 mm rail (EN 60715).

Connections

  • Inputs 1-4: the input terminal block on the top edge.
  • KNX bus: the red/black bus terminal on the bottom edge (− +).

Screw terminals take 0.5-2.5 mm², torque max. 0.4 N·m. For the full ratings, see the Datasheet.

Mounting and wiring

  1. Clip the device onto the DIN rail.
  2. Wire your contacts to the input terminals.
  3. Connect the KNX bus to the bus terminal.

The device scans its inputs at more than 12 V DC with an input current of 0.7 mA. Keep each run to 100 m or less at a cross section of 1.5 mm².

WARNING

The inputs supply their own scanning voltage. Connect floating (dry) contacts only.

Atios Binary4 ADK-B4 Datasheet
  1. 1KNX bus connection terminal
  2. 2Programming LED
  3. 3Programming button
  4. 4Input connection terminals