Buttons & LED Codes
The Heat6 has six channel buttons with status LEDs, an All-on and an All-off button, a Man./Auto. button with LED, and a Programming button with LED, all on the front of the device.
Programming LED codes
| LED | State | Meaning |
|---|---|---|
| 🔴 | Solid | Programming mode active, assigning the physical address |
| 🟢 | Blinking | Application running normally |
Channel LED codes
| LED | State | Meaning |
|---|---|---|
| 🟢 | Solid | Valve open |
| ⚫ | Off | Valve closed |
| 🟢 | Blinking, 1 s on and 1 s off | Short circuit, overload or undervoltage on that output |
Manual / Auto
Press and hold the Man./Auto. button for one second to switch between manual and automatic operation. The LED is on in manual mode and off in automatic mode. The device can also return to automatic after 10 to 6000 seconds without a button press.
Manual operation has to be enabled in ETS before the buttons work.
Channel buttons
Each channel button opens and closes the valve on that channel. All-on opens all six valves, All-off closes them.
TIP
Manual and forced operation take priority over a valve purge and cancel it. See Valve Outputs.