Skip to content

Room Controllers ​

The Heat6 contains six room temperature controllers. Each one is configured on its own, can be given a name of up to 30 characters, and drives either a valve output on the same device or an actuator elsewhere on the bus.

Temperature reference ​

A controller reads its room temperature from one external sensor, or from two external sensors combined with a weighting from 10:90 to 90:10. If one of the two fails, the controller uses the other. The device sends a read request to the sensors after a download and after voltage recovery, and can poll them cyclically.

If the temperature is unavailable, the controller falls back to a configured control value, set separately for summer and winter when summer/winter mode is enabled.

Heating and cooling ​

A controller runs in heating mode, cooling mode, or both. In combined mode you choose how it changes over, either from a bus object or automatically once the temperature passes the setpoint by an upper or lower dead zone of 0.5-10 K. The controller supports 2-pipe systems, where one valve carries both hot and cold water, and 4-pipe systems, where heating and cooling have separate valves.

With summer/winter mode enabled, the changeover can be limited so that only cooling runs in summer and only heating in winter.

Control types ​

  • 2-point: switches on and off around the setpoint, with a separate upper and lower hysteresis of 0-20 K. A small hysteresis holds the temperature tighter but sends more telegrams.
  • PWM with PI control: sends on and off telegrams whose duty cycle follows the PI control value, over a cycle of 1-255 minutes.
  • Continuous with PI control: sends the control value as a percentage, on change and cyclically.

The PI response comes from a preset: hot water heating, underfloor heating, electrical heating, cooling ceilings, split units or fan coil units. You can also set it by hand, with a proportional range of 1-10 K and a reset time of 0-255 minutes.

Operation modes and setpoints ​

Each controller supports comfort, standby, economy and frost/heat protection, switched by 1-bit or 1-byte objects. Comfort can also be extended for a set time, after which the controller returns to the previous mode.

Setpoints are defined in one of two ways:

  • Relative: a base setpoint for comfort, with standby and economy derived from it by a fixed offset for heating and cooling.
  • Absolute: an independent setpoint for every mode.

The setpoint can also be shifted by an additional offset in steps of 0.5 K or 1 K, within limits you set. Every setpoint stays inside the configured minimum and maximum of 5-37 °C. The frost and heat protection setpoints are set in ETS only and are not limited by that range.

Window contacts and presence ​

A window contact switches the controller to economy or to frost/heat protection after a delay, and returns it to the previous mode when the window is closed. A presence signal from the bus switches the controller to comfort and releases it again when presence ends. Telegrams that arrive in the meantime are recorded and applied afterwards.

Scenes ​

Each controller has five scenes, each assigned a scene number from 1 to 64. A scene sets the operation mode, or the setpoint temperature when operation modes are disabled. Scenes are recalled and stored from the bus, and a stored scene survives a bus voltage failure.