Shutter
Setup
- Go to Accessory Manager
- Click the + icon and select Shutter
- Enter a name for the accessory
- Enter the KNX group addresses
KNX Group Addresses
| Characteristic | Control | Status | Datatype |
|---|---|---|---|
| Movement | 0/0/1 | 0/0/4 | DPT-1 |
| Stop | 0/0/2 | n/a | DPT-1 |
| TargetPosition | 0/0/3 | n/a | DPT-5 |
| CurrentPosition | n/a | 0/0/4 | DPT-5 |
| TargetTilt | 0/0/5 | n/a | DPT-5 |
| CurrentTilt | n/a | 0/0/6 | DPT-5 |
Descriptions
| Group Address | Description | Datatype |
|---|---|---|
| 0/0/1 | Long Up/Down, opens or closes the shutter completely | DPT-1 |
| 0/0/2 | Short Up/Down, step moves the shutter and/or adjusts tilt angle | DPT-1 |
| 0/0/3 | Position, moves shutter to a fixed position between 0–100% | DPT-5 |
| 0/0/4 | Position status, current position of the shutter | DPT-5 |
| 0/0/5 | Tilt Position, rotates slats to a fixed angle between 0–100% | DPT-5 |
| 0/0/6 | Tilt Position status, current tilt angle between 0–100% | DPT-5 |