DALI Monitor
The DALI Monitor shows every frame on the DALI bus, live. Use it to check that a command reaches the bus and to see which device sends which event.
- Open the Web Interface of your SmartCore and go to DALI Monitor.
- Click Start. New frames appear at the top of the list. Click Stop to end the capture.
- In the ⋮ menu, click Export Frames to save the capture as a file, Import Frames to open a saved capture, or Clear Frames to empty the list.
Columns
| Column | Meaning |
|---|---|
| N | Number of the frame in the capture |
| Type | Type of frame, see the next table |
| Frame | The frame as hex bytes |
| Address | The device or instance the frame is for or from |
| Command | The command, answer or event in plain text |
| Date, Time | When the SmartCore received the frame |
| Delta | Time since the previous frame |
Frame types
| Type | Meaning |
|---|---|
| DALI16 DAP | Sets a light to a level, for example DIRECT ARC POWER 254 (100%) |
| DALI16 IAP | Command to a light that sends no answer, for example OFF, SET MAX LEVEL or ADD TO GROUP |
| DALI16 Query | Question to a light, for example QUERY STATUS |
| DALI16 Special | Command without an address, for example TERMINATE or DTR0 |
| DALI16 App Ext | Command for one device type, for example a colour command |
| DALI16 Answer | Answer of a device to a question |
| DALI24 Command | Command to an input (control device), for example IDENTIFY DEVICE |
| DALI24 Event | Event from an input, for example a button press or a light reading |
Addresses
| Address | Meaning |
|---|---|
| A0 to A63 | Short address of a device |
| Bcast | Broadcast to all devices |
| Special | Special command, no address |
| A0, Dev | The device at A0 as a whole |
| A0, iN0 | Instance number 0 of the device at A0 |
| iT4, iN1 | Instance type 4, instance number 1 |
An instance is one button or sensor inside an input. For example, the Atios DALI-2 Button Coupler has four push button instances.
Event numbers
In a DALI24 Event row, the Command column shows Event and a number. What the number means depends on the instance type (iT) in the Address column.
| Instance type | Event | Meaning |
|---|---|---|
| iT1 Push button | 0 | Button released |
| iT1 Push button | 1 | Button pressed |
| iT1 Push button | 2 | Short press |
| iT1 Push button | 5 | Double press |
| iT1 Push button | 9 | Long press start |
| iT1 Push button | 11 | Long press repeat, sent again while the button is held |
| iT1 Push button | 12 | Long press stop |
| iT1 Push button | 14 | Button free again after it was stuck |
| iT1 Push button | 15 | Button stuck |
| iT2 Absolute input, for example a slider or rotary switch | up to 1023 | Position. The SmartCore cannot tell which kind of input it is and treats it as a rotary encoder. The range depends on the resolution of the input. |
| iT3 Occupancy sensor | +1 | Movement (without +1: no movement) |
| iT3 Occupancy sensor | +2 | Occupied (without +2: vacant) |
| iT3 Occupancy sensor | +4 | Repeat report: still occupied or still vacant |
| iT3 Occupancy sensor | +8 | Sent by a movement sensor (without +8: presence sensor) |
| iT4 Light sensor | up to 1023 | Measured light value. How many lux one step is depends on the sensor, see its datasheet. |
For an occupancy sensor, add the values. For example, Event 3 means occupied with movement, and Event 6 means still occupied without movement.
For a light sensor, the number is a reading, not a code. For example, Event 47 at iT4, iN1 means the sensor measured the light value 47.